2.3Düşük

CVE-2026-124760Alarm receiver stops delivering alarms after a malformed alarm notification

RT-Labs P-Net Yayım: (5 gün önce)

Açıklama

P-Net before 1.0.4 sets the alarm receiver state to waiting for confirmation before the data of a received alarm notification is parsed. If the parsing fails the state is not restored, and later alarm notifications of the same priority are discarded without acknowledge until the Application Relationship is released. The Application Relationship and the cyclic data exchange keep working. The attacker must be able to send an alarm notification in the context of an established Application Relationship and requires ADJACENT network access.

Zayıflık türü (CWE): CWE-754

Veri: CVE.org, NVD, CISA KEV, FIRST EPSS, Ubuntu. Bilgiler kaynaktaki haliyle, İngilizce yayımlanır.

Etkilenen ürünler ve sürümler

ÜreticiÜrünSürümler
RT-Labs P-Net < 1.0.4