8.7Yüksek
CVE-2025-9041Rockwell Automation FLEX 5000 I/O - Module Fault
Açıklama
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
Zayıflık türü (CWE):
CWE-1287
Veri: CVE.org, NVD, CISA KEV, FIRST EPSS, Ubuntu. Bilgiler kaynaktaki haliyle, İngilizce yayımlanır.
Etkilenen ürünler ve sürümler
| Üretici | Ürün | Sürümler | |
|---|---|---|---|
| Rockwell Automation | FLEX 5000 I/O | Version 2.011 or below |