7 results
6.5Medium
CVE-2026-8067
Hitachi Energy RTU500 series CMU firmware

An improper authorization vulnerability in the end-of-life versions of RTU500’s web application allows an authenticated user to trigger the RTU500 to reboot through the reset endpoint. Successful exploitation could cause temporary device unavailability and di…

9.1Critical
CVE-2026-8066
Hitachi Energy RTU500 series CMU firmware

A directory traversal vulnerability in the file upload functionality of Hitachi Energy RTU500 end-of-life versions allows an unauthenticated attacker to write or overwrite arbitrary files on the device file system. Depending on the files affected, successful …

9.1Critical
CVE-2026-8065
Hitachi Energy RTU500 series CMU firmware

An authentication bypass vulnerability in the firmware update endpoint of Hitachi Energy RTU500 end-of-life versions allows an unauthenticated attacker to upload arbitrary firmware through a crafted POST request. Successful exploitation could allow the attack…

5.9Medium
CVE-2026-17539
Hitachi Energy RTU500 series CMU firmware

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection…

6.9Medium
CVE-2026-8479
Hitachi Energy RTU500 series CMU firmware

IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 function…

8.7High
CVE-2026-1773
Hitachi Energy RTU500 series CMU firmware

IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not rem…

5.3Medium
CVE-2026-1772
Hitachi Energy RTU500 series CMU firmware

RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.