A vulnerability exists in SYS600 RBAC mechanism where users having access to the engineering tools could elevate their privileges to administrator level on the underlying Windows host, granting themselves full control over the host machine.
hitachienergy Schwachstellen (CVE)
Für hitachienergy veröffentlichte CVE-Einträge, neueste zuerst. Folgen Sie, um bei neuen Einträgen eine E-Mail zu erhalten.
A vulnerability exists in SYS600 which allows any user authenticated to the operating system of the server hosting the application to read and modify application objects without being authenticated to the SYS600 system itself. Only the SYS600 system users sh…
A CSV injection vulnerability exists in SYS600. Injected malicious formulas can add or modify data to the spreadsheet, insert links, exfiltrate data, and in some cases, depending on how the user has their environment configured, execute malicious code on the …
A vulnerability exists in REB500 for an authenticated user with low-level privileges to access and alter the content of directories by using the DAC protocol that the user is not authorized to do so.
A vulnerability exists in REB500 for an authenticated user with Installer role to access and alter the contents of directories that the role is not authorized to do so.
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not rem…
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.
A vulnerability exists in the IEC 61850 in MicroSCADA X SYS600 product. The certificate validation of the TLS protocol allows remote Man-in-the-Middle attack due to missing proper validation.
A vulnerability exists in the Web interface of the MicroSCADA X SYS600 product. The filtering query in the Web interface can be malformed, so returning data can leak unauthorized information to the user.
A vulnerability exists in the IEC 61850 of the MicroSCADA X SYS600 product. An IEC 61850-8 crafted message content from IED or remote system can cause a denial of service resulting in disconnection loop.
A vulnerability exists in in the Monitor Pro interface of the MicroSCADA X SYS600 product. An authenticated user with low privileges can see and overwrite files causing information leak and data corruption.
A vulnerability exists in MicroSCADA X SYS600 product. If exploited this could allow a local unauthenticated attacker to tamper a system file, making denial of Notify service.
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is …
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license f…